VFD Fault Diagnosis and Troubleshooting Guide

VFD Fault Diagnosis & Troubleshooting Guide | Common VFD Alarms, Causes, and Solutions ⚙️

Welcome to Insight Control System Blog page.

Introduction:

Variable Frequency Drives (VFDs) play a critical role in modern industrial automation by controlling motor speed, torque, and energy efficiency. However, VFD faults and alarms can interrupt operations, reduce productivity, and damage equipment if not addressed correctly.⚠️

VFD Fault and Solution
VFD Fault Diagnosis and Troubleshooting Guide

This comprehensive VFD fault diagnosis and troubleshooting guide explains common VFD alarms, root causes, and step-by-step solutions, helping maintenance engineers, technicians, and automation professionals quickly restore normal operation and improve system reliability.

1. Current Limit 🔧

The drive enters current limit mode. This means the motor current has reached the set limit.
VFD Fault Diagnosis and Troubleshooting Guide
Current Limit

👉Check Current Limit Settings.

✅ If Yes (If OK): 
Check Motor, Load, and Drive Size.
Verify:
  • Motor rating matches the drive,
  • Mechanical load is not excessive,
  • Drive capacity is sufficient for the application,
If No (If Not-OK):
Correct Settings
Adjust current limit parameters to proper values.

▶️ Restart the Drive

👉Check Current Limit?

If Yes (If OK): 
Perform Motor Identification
  • Run motor auto-tuning / identification.
  • This allows the drive to correctly control motor current.
❌ If No (If Not-OK):
▶️ Restart the Drive

────────────────

2. Drive Not Getting to Speed 🚀  

Start when the VFD fails to reach the commanded speed.

VFD Fault Diagnosis and Troubleshooting Guide
Drive Not Getting to Speed

👉Check Current Limit or DC Bus Limit

✅ If Yes (If OK):
Check Motor current
DC bus voltage
If motor current is OK and DC bus voltage is OK → Continue checking.
If motor current or DC bus voltage is NOT OK → Investigate and correct the issue.
Finally check the Speed.

❌ If No (If Not-OK): Continue Next Process

👉Check Analog Input Reading

Is the analog input signal being read correctly?

✅ If Yes (If OK): Continue Next Process

❌ If No (If Not-OK): Check wiring
  • Loose terminals
  • Damaged cable
  • Wrong polarity
  • Incorrect signal type
Finally check the Speed.

👉Check Reference Source Settings

✅ If Yes (If OK): Continue Next Process

❌ If No (If Not-OK): 
Correct the reference source settings.
Finally check the Speed.

👉Check For Preset Speed Command

✅ If Yes (If OK): Remove fixed speed (preset speed) command.

❌ If No (If Not-OK): check the Speed.

🔎Check Speed:
Verify that the drive receives the correct frequency reference and accelerates normally after all corrections.

────────────────

3. VFD Drive Does Not Start ⏳

VFD Fault Diagnosis and Troubleshooting Guide
VFD Drive Does Not Start

👉Check if the Drive is Ready?

✅ If Yes (If OK):Continue Next Process.

❌ If No (If Not-OK):
Check for Active Fault
If a fault exists, then clear the fault,

If Yes (If OK): 
check DC Bus voltage.

If Yes (If OK):
Ensure Run Enable input is active.

If Yes (If OK):
▶️ Restart the Drive.

👉Check Start Source Settings

✅ If Yes (If OK):Continue Next Process.

❌ If No (If Not-OK):
Correct the start source settings.
Next Restart the drive.

👉Check the Control Place (Control Source)

✅ If Yes (If OK):Continue Next Process.

❌ If No (If Not-OK):
Correct Settings.
Next Restart the drive.

👉Check the Start Signal

✅ If Yes (If OK):Restart the drive.

❌ If No (If Not-OK):
Ensure the start command is active and check wiring
  • Loose terminals
  • Open contact
  • Incorrect input type
  • Damaged cable
Restart Drive:
Once all checks are correct:
  • Restart the drive
  • Verify the RUN command
  • Confirm that the drive starts normally
────────────────

4. Ground Fault Detected ⏚ 

VFD Fault Diagnosis and Troubleshooting Guide
Ground Fault Detected

👉Check Motor Leads

✅ If Yes (If OK):Continue Next Process.

❌ If No (If Not-OK): Correct Cabling
  • Fix loose wires
  • Replace damaged cables
  • Verify phase sequence
  • Check insulation
▶️Next Restart the drive.

👉Disconnect Motor Leads & Restart Drive

Disconnect the motor from the drive and restart the VFD.
This helps determine whether the fault is coming from the motor or the drive.

👉Check Again: Is Ground Fault Still Present?

❌ If No (If Not-OK):
  • Check the Motor
  • Motor insulation test (Megger)
  • Check for winding short-to-ground
  • Replace or repair the motor
  • You may also test the drive using a known good motor
▶️Next Restart the drive.

✅ If Yes (If OK):Current Measurement Fault in Drive
If the drive shows ground fault even with motor disconnected:
This indicates:
  • Internal current-sensing failure
  • Internal short
  • Faulty IGBT module
  • Drive control board issue
This generally requires:
  • Drive repair
  • Component replacement
  • Drive replacement (if not repairable)
  • After correcting the issue (motor or drive), restart the VFD and test operation.
────────────────

5. Input Phase Fault Detected 🔌

The drive has detected an input phase loss or imbalance.

VFD Fault Diagnosis and Troubleshooting Guide
Input Phase Fault Detected

👉 Check Line Voltage

❌ If No (If Not-OK):
Correct Input Voltage
  • Fix supply imbalance
  • Restore missing phase
  • Correct loose terminals
  • Restore proper mains connection
▶️Then Restart the drive.

✅ If Yes (If OK):Continue Next Process.

👉 Static Checks OK?

Perform Static Checks this includes checking:
  • Input fuses
  • Input rectifier
  • Contactor connections
  • Supply wiring continuity
  • Phase sequence
❌ If No (If Not-OK): 
Replace Faulty Components
Possible faults include:
  • Blown fuses
  • Damaged rectifier module
  • Burnt terminals
  • Open-phase wiring
  • After repairs, 
▶️Then Restart the drive.

✅ If Yes (If OK):Continue Next Process.

👉 Input Phase Fault

❌ If No (If Not-OK):
Check for Input Phase Fault Again,
System is normal after correction.

▶️Then Restart the drive.

✅ If Yes (If OK):
The issue is internal to the drive.
Proceed to next step.

👉 Measurement Fault in Drive

If the drive shows input phase fault even after voltage and static checks:
The drive has a faulty phase measurement circuit.
Possible causes:
  • Faulty input current sensors
  • Defective control board
  • Faulty measurement IC
This requires:
  • Drive repair
  • Component replacement
  • Or complete drive replacement (if repair is not possible)
────────────────

6. Motor Over Temperature Alarm🌡️

The VFD reports that the motor temperature is too high or thermal protection has been triggered.
VFD Fault Diagnosis and Troubleshooting Guide
Motor Over Temperature Alarm

👉Check Motor Parameters is OK?

Are the motor parameters set correctly?
Examples include:
  • Motor rated current
  • Motor thermal class
  • Motor power (kW/HP)
  • Motor frequency and voltage
  • Motor thermal settings
❌ If No (If Not-OK): 
Correct Parameters
Enter the correct motor nameplate data and thermal settings,
 
▶️Then Restart the drive.

✅ If Yes (If OK):Continue Next Process.

👉Check for Motor Overload Condition

Motor overload may happen due to:
  • Heavy mechanical load
  • Blocked fan/pump
  • High friction or jamming
  • Low cooling airflow
  • Incorrect speed setting
❌ If No (If Not-OK):
Check Motor Thermal Overload Parameters
Ensure that:
  • Thermal model settings are correct
  • No false overload conditions
  • Cooling fan and airflow are normal
▶️Then Restart the drive.

✅ If Yes (If OK):Reduce Motor Load:
If actual overload is confirmed, Reduce the load by:
  • Removing mechanical blockage
  • Reducing torque demand
  • Fixing jammed equipment
  • Improving motor cooling
  • Adjusting process load
▶️Once load is corrected Restart the drive.

────────────────

7. Output phase fault⚠️

VFD Fault Diagnosis and Troubleshooting Guide
Output phase fault

👉Disconnect Motor Leads 

Disconnect the motor cables from the drive output terminals. 
This isolates the motor and wiring from the drive.

👉Output Phase Fault?

❌ If No (If Not-OK): Check Motor and Connections
Fault is caused by:
  • Motor winding problem,
  • Cable damage,
  • Loose or incorrect wiring,
  • Ground fault or insulation failure,
▶️ Restart Drive
  • After correcting motor or wiring issues, restart the drive.
  • System should run normally.
✅ If Yes (If OK):
Faulty Current Measurement
Fault is internal to the drive.
Possible causes:
  • Faulty current sensor,
  • Defective IGBT/output stage,
  • Power module or control PCB failure,
After restart the drive. If fault remains, drive requires service or replacement.
────────────────

8. Over Current 🔌

The drive trips due to an over current fault.
VFD Fault Diagnosis and Troubleshooting Guide
Over Current

👉Check Motor Settings

Check whether the motor parameters in the drive are correct:
  • Rated voltage
  • Rated current
  • Rated power (kW/HP)
  • Frequency
❌ If No (If Not-OK):
Correct Settings
  • Enter the correct motor nameplate values in the drive.
▶️ Restart Drive
  • After correcting the settings, restart the drive.
  • Fault should be cleared.
✅ If Yes (If OK):
Disconnect Motor Leads, Restart Drive
  • Disconnect motor cables from the drive.
  • Restart the drive without the motor connected.
  • This helps isolate the fault.

👉Over Current

✅ If Yes (If OK): Current Measurement Fault in Drive.
The fault is inside the drive.
Possible causes:
  • Faulty current sensor,
  • Damaged IGBT or power module, Internal control board issue,
Restart Drive
  • Drive needs repair or replacement before normal operation.
❌ If No (If Not-OK): Check Motor, Load, and Drive Size
The drive is OK.
Possible issues:
  • Motor mechanical load is too high,
  • Motor problem (bearing, winding), 
  • Drive size is too small for the motor.
▶️ Restart Drive
  • After fixing motor/load issues, 
  • restart the drive.
────────────────

9. Over Voltage ⚡

The drive trips due to an over-voltage fault.
This happens when the DC bus voltage exceeds the safe limit.
VFD Fault Diagnosis and Troubleshooting Guide
Over Voltage

👉Line Voltage OK?

✅ If Yes (If OK):
Fault Occurs During Deceleration or When Motor Is Over-Running?

❌ If No (If Not-OK):
Correct Input Voltage
  • Check incoming supply voltage.
  • Ensure voltage is within the drive’s rated limits.
▶️ Restart Drive.

👉Fault Occurs During Deceleration or When Motor Is Over-Running?

✅ If Yes (If OK):
Increase Deceleration Time or Add Brake Chopper
  • Fast deceleration causes regenerated energy to raise DC voltage.
Solution:
  • Increase deceleration time, or Use a braking resistor / brake chopper.
▶️ Restart Drive

❌ If No (If Not-OK): Monitor = Measured Value

👉Monitor = Measured Value

✅ If Yes (If OK): Check Line Side Harmonics
  • Voltage spikes or harmonics from the power supply may cause over-voltage.
Check:
  • Power quality,
  • Harmonic distortion,
  • Line reactors or filters,
▶️ Restart Drive

❌ If No (If Not-OK): Measurement Fault in Drive
  • The voltage feedback or sensing circuit inside the drive is faulty.
  • Drive requires repair or replacement.
▶️ Restart Drive

────────────────

10. Under Voltage ⚡

The drive trips due to an under-voltage fault.
This means the supply or DC bus voltage is below the required level.

VFD Fault Diagnosis and Troubleshooting Guide
Under Voltage

👉Line Voltage OK?

✅ If Yes (If OK): Continue Next Process Static Checks OK?

❌ If No (If Not-OK):
Correct Input Voltage
  • Check incoming power supply.
  • Ensure voltage is within the drive’s rated limits.
▶️Restart Drive

👉Static Checks OK?

✅ If Yes (If OK): Continue Next Process [ Monitor = Measured Value?]

❌ If No (If Not-OK):
Replace Faulty Components
Possible issues:
  • Blown fuses,
  • Loose terminals,
  • Faulty rectifier or DC bus components,
▶️ Restart Drive

👉Monitor = Measured Value?

✅ If Yes (If OK):
Check Power Quality and Proper Drive Sizing
Possible causes:
  • Voltage dips
  • Weak power supply
  • Drive undersized for the motor/load
▶️Restart Drive

❌ If No (If Not-OK):
Measurement Fault in Drive
  • Internal voltage sensing circuit is faulty.
  • Drive requires repair or replacement.
▶️Restart Drive

────────────────

11. Unit Over Temperature 🌡️

  • The drive trips due to over-temperature.
  • This happens when the internal temperature exceeds the safe limit.
VFD Fault Diagnosis and Troubleshooting Guide
Unit Over Temperature

👉Cooling Fan ON?

✅ If Yes (If OK): Continue Next Process [Heat Sink Clear?]

❌ If No (If Not-OK):
Repair Cooling Fan(s)
  • Check fan power supply.
  • Replace faulty or blocked cooling fans.
▶️Restart Drive

👉Heat Sink Clear?

✅ If Yes (If OK): Continue Next Process [ Monitor = Measured Value?]

❌ If No (If Not-OK):
Clean Heat Sink
  • Remove dust, dirt, or blockage.
  • Ensure proper airflow through the heat sink.
▶️ Restart Drive

👉Monitor = Measured Value?

✅ If Yes (If OK):
Measurement Fault in Drive
  • Temperature sensor or monitoring circuit is faulty.
  • Drive requires repair or replacement.
▶️ Restart Drive

❌ If No (If Not-OK):
Check Ambient Temperature of Inlet Air
  • Ensure surrounding temperature is within limits.
  • Improve ventilation or cooling in the panel/room.
▶️ Restart Drive

────────────────

Conclusion:

  • A systematic approach to VFD fault diagnosis significantly reduces downtime, protects equipment, and improves operational efficiency. 
  • By understanding alarm causes and following structured troubleshooting steps, technicians can quickly identify whether issues originate from the motor, load, power supply, or the drive itself. 
  • This guide serves as a practical reference for field engineers, maintenance teams, and automation professionals working with Variable Frequency Drives in industrial environments.

📎 Related: Danfoss FC-102 LCP Simulator Tool

📎 Related: How Programmable Logic Controller Works

📎 Related: Top 100+ Building Automation System Abbreviations and Their Meanings Part 1

📎 Related: QElectro Tech Software: Free Electrical Diagram Tool – Full Overview & Guide

📎 Related: PLC Basic Instructions Explained | Essential Allen-Bradley MicroLogix & PLC-5 Ladder Logic Functions


🌐 Follow Us Online

       

Comments