Correct Settings
Adjust current limit parameters to proper values.
▶️ Restart the Drive
👉Check Current Limit?
✅ If Yes (If OK):
Perform Motor Identification
- Run motor auto-tuning / identification.
- This allows the drive to correctly control motor current.
❌ If No (If Not-OK):
▶️ Restart the Drive
────────────────
2. Drive Not Getting to Speed 🚀
Start when the VFD fails to reach the commanded speed.
 |
| Drive Not Getting to Speed |
👉Check Current Limit or DC Bus Limit
✅ If Yes (If OK):
Check Motor current
DC bus voltage
If motor current is OK and DC bus voltage is OK → Continue checking.
If motor current or DC bus voltage is NOT OK → Investigate and correct the issue.
Finally check the Speed.
❌ If No (If Not-OK): Continue Next Process
👉Check Analog Input Reading
Is the analog input signal being read correctly?
✅ If Yes (If OK): Continue Next Process
❌ If No (If Not-OK): Check wiring
- Loose terminals
- Damaged cable
- Wrong polarity
- Incorrect signal type
Finally check the Speed.
👉Check Reference Source Settings
✅ If Yes (If OK): Continue Next Process
❌ If No (If Not-OK):
Correct the reference source settings.
Finally check the Speed.
👉Check For Preset Speed Command
✅ If Yes (If OK): Remove fixed speed (preset speed) command.
❌ If No (If Not-OK): check the Speed.
🔎Check Speed:
Verify that the drive receives the correct frequency reference and accelerates normally after all corrections.
────────────────
3. VFD Drive Does Not Start ⏳
 |
| VFD Drive Does Not Start |
👉Check if the Drive is Ready?
✅ If Yes (If OK):Continue Next Process.
❌ If No (If Not-OK):
Check for Active Fault
If a fault exists, then clear the fault,
If Yes (If OK):
check DC Bus voltage.
If Yes (If OK):
Ensure Run Enable input is active.
If Yes (If OK):
▶️ Restart the Drive.
👉Check Start Source Settings
✅ If Yes (If OK):Continue Next Process.
❌ If No (If Not-OK):
Correct the start source settings.
Next Restart the drive.
👉Check the Control Place (Control Source)
✅ If Yes (If OK):Continue Next Process.
❌ If No (If Not-OK):
Correct Settings.
Next Restart the drive.
👉Check the Start Signal
✅ If Yes (If OK):Restart the drive.
❌ If No (If Not-OK):
Ensure the start command is active and check wiring
- Loose terminals
- Open contact
- Incorrect input type
- Damaged cable
Restart Drive:
Once all checks are correct:
- Restart the drive
- Verify the RUN command
- Confirm that the drive starts normally
────────────────
4. Ground Fault Detected ⏚
 |
| Ground Fault Detected |
👉Check Motor Leads
✅ If Yes (If OK):Continue Next Process.
❌ If No (If Not-OK): Correct Cabling
- Fix loose wires
- Replace damaged cables
- Verify phase sequence
- Check insulation
▶️Next Restart the drive.
👉Disconnect Motor Leads & Restart Drive
Disconnect the motor from the drive and restart the VFD.
This helps determine whether the fault is coming from the motor or the drive.
👉Check Again: Is Ground Fault Still Present?
❌ If No (If Not-OK):
- Check the Motor
- Motor insulation test (Megger)
- Check for winding short-to-ground
- Replace or repair the motor
- You may also test the drive using a known good motor
▶️Next Restart the drive.
✅ If Yes (If OK):Current Measurement Fault in Drive
If the drive shows ground fault even with motor disconnected:
This indicates:
- Internal current-sensing failure
- Internal short
- Faulty IGBT module
- Drive control board issue
This generally requires:
- Drive repair
- Component replacement
- Drive replacement (if not repairable)
- After correcting the issue (motor or drive), restart the VFD and test operation.
────────────────
5. Input Phase Fault Detected 🔌
The drive has detected an input phase loss or imbalance.
 |
| Input Phase Fault Detected |
👉 Check Line Voltage
❌ If No (If Not-OK):
Correct Input Voltage
- Fix supply imbalance
- Restore missing phase
- Correct loose terminals
- Restore proper mains connection
▶️Then Restart the drive.
✅ If Yes (If OK):Continue Next Process.
👉 Static Checks OK?
Perform Static Checks this includes checking:
- Input fuses
- Input rectifier
- Contactor connections
- Supply wiring continuity
- Phase sequence
❌ If No (If Not-OK):
Replace Faulty Components
Possible faults include:
- Blown fuses
- Damaged rectifier module
- Burnt terminals
- Open-phase wiring
- After repairs,
▶️Then Restart the drive.
✅ If Yes (If OK):Continue Next Process.
👉 Input Phase Fault
❌ If No (If Not-OK):
Check for Input Phase Fault Again,
System is normal after correction.
▶️Then Restart the drive.
✅ If Yes (If OK):
The issue is internal to the drive.
Proceed to next step.
👉 Measurement Fault in Drive
If the drive shows input phase fault even after voltage and static checks:
The drive has a faulty phase measurement circuit.
Possible causes:
- Faulty input current sensors
- Defective control board
- Faulty measurement IC
This requires:
- Drive repair
- Component replacement
- Or complete drive replacement (if repair is not possible)
────────────────
6. Motor Over Temperature Alarm🌡️
The VFD reports that the motor temperature is too high or thermal protection has been triggered.
 |
| Motor Over Temperature Alarm |
👉Check Motor Parameters is OK?
Are the motor parameters set correctly?
Examples include:
- Motor rated current
- Motor thermal class
- Motor power (kW/HP)
- Motor frequency and voltage
- Motor thermal settings
❌ If No (If Not-OK):
Correct Parameters
Enter the correct motor nameplate data and thermal settings,
▶️Then Restart the drive.
✅ If Yes (If OK):Continue Next Process.
👉Check for Motor Overload Condition
Motor overload may happen due to:
- Heavy mechanical load
- Blocked fan/pump
- High friction or jamming
- Low cooling airflow
- Incorrect speed setting
❌ If No (If Not-OK):
Check Motor Thermal Overload Parameters
Ensure that:
- Thermal model settings are correct
- No false overload conditions
- Cooling fan and airflow are normal
▶️Then Restart the drive.
✅ If Yes (If OK):Reduce Motor Load:
If actual overload is confirmed, Reduce the load by:
- Removing mechanical blockage
- Reducing torque demand
- Fixing jammed equipment
- Improving motor cooling
- Adjusting process load
▶️Once load is corrected Restart the drive.
────────────────
7. Output phase fault⚠️
 |
| Output phase fault |
👉Disconnect Motor Leads
Disconnect the motor cables from the drive output terminals.
This isolates the motor and wiring from the drive.
👉Output Phase Fault?
❌ If No (If Not-OK): Check Motor and Connections
Fault is caused by:
- Motor winding problem,
- Cable damage,
- Loose or incorrect wiring,
- Ground fault or insulation failure,
▶️ Restart Drive
- After correcting motor or wiring issues, restart the drive.
- System should run normally.
✅ If Yes (If OK):
Faulty Current Measurement
Fault is internal to the drive.
Possible causes:
- Faulty current sensor,
- Defective IGBT/output stage,
- Power module or control PCB failure,
After restart the drive. If fault remains, drive requires service or replacement.
────────────────
8. Over Current 🔌
The drive trips due to an over current fault.
 |
| Over Current |
👉Check Motor Settings
Check whether the motor parameters in the drive are correct:
- Rated voltage
- Rated current
- Rated power (kW/HP)
- Frequency
❌ If No (If Not-OK):
Correct Settings
- Enter the correct motor nameplate values in the drive.
▶️ Restart Drive
- After correcting the settings, restart the drive.
- Fault should be cleared.
✅ If Yes (If OK):
Disconnect Motor Leads, Restart Drive
- Disconnect motor cables from the drive.
- Restart the drive without the motor connected.
- This helps isolate the fault.
👉Over Current
✅ If Yes (If OK): Current Measurement Fault in Drive.
The fault is inside the drive.
Possible causes:
- Faulty current sensor,
- Damaged IGBT or power module, Internal control board issue,
Restart Drive
- Drive needs repair or replacement before normal operation.
❌ If No (If Not-OK): Check Motor, Load, and Drive Size
The drive is OK.
Possible issues:
- Motor mechanical load is too high,
- Motor problem (bearing, winding),
- Drive size is too small for the motor.
▶️ Restart Drive
- After fixing motor/load issues,
- restart the drive.
────────────────
9. Over Voltage ⚡
The drive trips due to an over-voltage fault.
This happens when the DC bus voltage exceeds the safe limit.
 |
| Over Voltage |
👉Line Voltage OK?
✅ If Yes (If OK):
Fault Occurs During Deceleration or When Motor Is Over-Running?
❌ If No (If Not-OK):
Correct Input Voltage
- Check incoming supply voltage.
- Ensure voltage is within the drive’s rated limits.
▶️ Restart Drive.
👉Fault Occurs During Deceleration or When Motor Is Over-Running?
✅ If Yes (If OK):
Increase Deceleration Time or Add Brake Chopper
- Fast deceleration causes regenerated energy to raise DC voltage.
Solution:
- Increase deceleration time, or Use a braking resistor / brake chopper.
▶️ Restart Drive
❌ If No (If Not-OK): Monitor = Measured Value
👉Monitor = Measured Value
✅ If Yes (If OK): Check Line Side Harmonics
- Voltage spikes or harmonics from the power supply may cause over-voltage.
Check:
- Power quality,
- Harmonic distortion,
- Line reactors or filters,
▶️ Restart Drive
❌ If No (If Not-OK): Measurement Fault in Drive
- The voltage feedback or sensing circuit inside the drive is faulty.
- Drive requires repair or replacement.
▶️ Restart Drive
────────────────
10. Under Voltage ⚡
The drive trips due to an under-voltage fault.
This means the supply or DC bus voltage is below the required level.
 |
| Under Voltage |
👉Line Voltage OK?
✅ If Yes (If OK): Continue Next Process Static Checks OK?
❌ If No (If Not-OK):
Correct Input Voltage
- Check incoming power supply.
- Ensure voltage is within the drive’s rated limits.
▶️Restart Drive
👉Static Checks OK?
✅ If Yes (If OK): Continue Next Process [ Monitor = Measured Value?]
❌ If No (If Not-OK):
Replace Faulty Components
Possible issues:
- Blown fuses,
- Loose terminals,
- Faulty rectifier or DC bus components,
▶️ Restart Drive
👉Monitor = Measured Value?
✅ If Yes (If OK):
Check Power Quality and Proper Drive Sizing
Possible causes:
- Voltage dips
- Weak power supply
- Drive undersized for the motor/load
▶️Restart Drive
❌ If No (If Not-OK):
Measurement Fault in Drive
- Internal voltage sensing circuit is faulty.
- Drive requires repair or replacement.
▶️Restart Drive
────────────────
11. Unit Over Temperature 🌡️
- The drive trips due to over-temperature.
- This happens when the internal temperature exceeds the safe limit.
 |
| Unit Over Temperature |
👉Cooling Fan ON?
✅ If Yes (If OK): Continue Next Process [Heat Sink Clear?]
❌ If No (If Not-OK):
Repair Cooling Fan(s)
- Check fan power supply.
- Replace faulty or blocked cooling fans.
▶️Restart Drive
👉Heat Sink Clear?
✅ If Yes (If OK): Continue Next Process [ Monitor = Measured Value?]
❌ If No (If Not-OK):
Clean Heat Sink
- Remove dust, dirt, or blockage.
- Ensure proper airflow through the heat sink.
▶️ Restart Drive
👉Monitor = Measured Value?
✅ If Yes (If OK):
Measurement Fault in Drive
- Temperature sensor or monitoring circuit is faulty.
- Drive requires repair or replacement.
▶️ Restart Drive
❌ If No (If Not-OK):
Check Ambient Temperature of Inlet Air
- Ensure surrounding temperature is within limits.
- Improve ventilation or cooling in the panel/room.
▶️ Restart Drive
────────────────
Conclusion:
- A systematic approach to VFD fault diagnosis significantly reduces downtime, protects equipment, and improves operational efficiency.
- By understanding alarm causes and following structured troubleshooting steps, technicians can quickly identify whether issues originate from the motor, load, power supply, or the drive itself.
- This guide serves as a practical reference for field engineers, maintenance teams, and automation professionals working with Variable Frequency Drives in industrial environments.
Comments
Post a Comment