Temperature Sensor Installation Methods Part-1 | Immersion, Cable, Probe, Capillary & Averaging Sensors Explained
Welcome to Insight Control System Blogger page.
Introduction
- Temperature sensors play a critical role in Heating Ventilation Air Conditioning, building automation, and industrial systems. Proper installation ensures accurate temperature measurement, system safety, and long-term performance.
- In this article, we explore different temperature sensor installation methods, including immersion sensors, cable sensors, air probe sensors, capillary sensors, and averaging sensors.
- Each section explains sensor functionality, installation guidelines, and common applications helping technicians, engineers, and students understand best practices for reliable temperature monitoring.
☑️ Immersion sensors (Water)
- Temperature immersion sensors for water are designed to measure the temperature of liquids by being directly inserted into pipes, tanks, or water systems.
- These sensors provide highly accurate and fast temperature readings because they are in direct contact with the water.
- Immersion sensors typically include a protective stainless-steel probe and are installed using a pocket or well, allowing maintenance without draining the system.
- Their precise performance, durability, and ability to withstand continuous exposure to water make them essential for reliable temperature monitoring in both residential and commercial water applications.
Method of Installation
- Ensure that the full active length of the sensor is immersed in the medium.
- This is incorrect installation
| Method of Installation-1 |
Chilled water and refrigeration pipes:
To prevent condensation, extend the immersion pocket inside the lagging by use of a plastic sleeve.
| Chilled water and refrigeration pipes-1 |
The hole in the lagging must be sealed, to prevent the ingress of moisture (water-resistant seal).
| Chilled water and refrigeration pipes-2 |
1. Install sensors against the direction of flow.
2. Incorrect installation.
3. Install at the correct angle.
| Method of Installation-2 |
4. If the active length (a) of the sensor probe is longer than the diameter of the pipe, the sensor should be installed diagonally, or in a bypass pipe or bend.
| Method of Installation-3 |
5. The inlet side of the bypass pipe should project into the main pipe.
| Method of Installation-4 |
6. Maintain a clearance (distance A) between the sensor and any obstruction, so that there is room to remove the sensor from the immersion pocket.
| Method of Installation-5 |
7. For each sensing point, an additional immersion pocket, adjacent to the sensor, must be provided for test purposes.
8. Install outlet-temperature sensors directly at the heat exchanger outlet.
9. Sensors mounted without immersion pockets or with slotted or perforated immersion pockets must be identified accordingly. Attach a label marked: Installed without immersion pocket.
| Method of Installation-6 |
10. When mixing water at different temperatures, always maintain an adequate distance between the mixing point and the sensor (to take account of stratification).
| Method of Installation-7 |
Applications:
HVAC systems, boilers, chilled water lines, hot water supply systems, heat exchangers, and industrial process applications.
☑️ Cable sensors (Water)
| Temperature Cable sensors for Water |
- Temperature cable sensors for water are flexible, waterproof sensors designed to measure the temperature of water in pipes, tanks, and underwater environments.
- Unlike rigid probes, cable sensors use a sealed, durable cable with a sensing element at the tip, allowing easy installation in tight, curved, or hard-to-reach areas.
- These sensors provide reliable and accurate temperature readings while offering excellent resistance to moisture, corrosion, and continuous water exposure.
- Their flexibility, long cable lengths, and simple installation make them ideal for applications where standard immersion probes cannot be used.
Method of Installation
- The sensor element is not affected by orientation, but must be fully immersed in the medium to be measured (air or water).
- Use a file to ensure a smooth, clean contact surface, and fill the space between the sensor and the pipe with heat-conductive compound to improve thermal conductivity.
| Method of Installation |
Applications
HVAC systems, hot and chilled water lines, storage tanks, industrial processes, and environmental monitoring.
☑️ Probe sensors (Air)
| Temperature Probe Sensor |
- Temperature probe sensors for air are specialized devices designed to measure the temperature of airflow in ducts, ventilation systems, and open-air environments.
- These sensors feature a slim, durable probe that ensures fast response and accurate readings as air passes over the sensing element.
- Air temperature probe sensors help maintain proper climate control, improve energy efficiency, and ensure system performance by delivering real-time temperature data.
- Their robust design, quick installation, and precise measurement capabilities make them essential for monitoring air temperature in both commercial and industrial applications.
Method of Installation
1. Ensure that the full length of the sensor probe is exposed to the air flow.
2. A test hole must be provided adjacent to every sensor.
3. Do not use probe-type sensors in areas where stratification can occur (e.g. downstream of mixing dampers, heating coils, cooling coils or heat recovery units).
Averaging sensors should be considered.
| Method of Installation |
Applications
HVAC systems, building automation, clean rooms, air-handling units (AHUs), and industrial ventilation.
☑️ Capillary sensors with probes
| Temperature Capillary sensors with probes |
- Capillary sensors with probes are mechanical temperature-sensing devices that use a fluid-filled capillary tube connected to a sensing bulb or probe.
- When temperature changes, the fluid inside expands or contracts, creating a pressure change that activates a switch or control mechanism.
- Their simple design, high durability, and ability to sense temperature from a distance make them ideal for environments where electronic sensors may fail or where reliable mechanical operation is required.
- These sensors do not require external power.
Method of Installation
1. Install so that the device head is higher than the sensor probe.
2. The sensor probe should be tilted downwards.
3. The ambient temperature at the device head must always be higher than the temperature to which the sensor probe is exposed.
4. The sensor element must always point downwards.
Do not allow the capillary to form a U-shape.
| Method of Installation-1 |
5. Do not bend the capillary too tightly (radius of bend must not be less than 50 mm).
6. When routing the capillary through internal or external walls, for example, always use a lined and insulated conduit.
7. Any unused length of capillary should be neatly rolled.
8. Where the capillary passes through sheet metal, protect it with a rubber grommet (to prevent shearing).
| Method of Installation-1 |
Application
HVAC systems, boilers, heaters, refrigeration units, and industrial equipment for temperature control and safety cut-off applications.
☑️ Averaging sensors
| Temperature Averaging sensor |
- Averaging sensors are temperature sensors designed to measure the average temperature across a large area, such as inside air ducts or ventilation systems.
- Instead of reading temperature from a single point, these sensors use a long flexible sensing element often several meters in length to detect multiple temperature variations along the airflow path.
- They are commonly used in HVAC and building automation systems to ensure accurate control of supply and return air temperatures.
- Averaging sensors help prevent hot or cold spots, improve system efficiency, and provide more stable and reliable temperature control in large ducts or uneven airflow environments.
- Their flexible design makes them ideal for applications where air temperature varies significantly across the duct.
Method of Installation
1. Allow a distance of at least 50 mm between the heat exchanger and the sensor.
2. The entire length of an averaging sensor must be installed fully inside the air duct.
3. The sensor element must be distributed evenly over the full cross-section.
| Method of Installation-1 |
4. If air washers are used for humidification, install the sensor element downstream of the eliminator plate, in the direction of air flow.
| air washers are used for humidification |
5. Do not bend the capillary too tightly (radius of bend must not be less than 50 mm).
6. When routing the capillary through internal or external walls, for example, always use a lined and insulated conduit.
8. Where the capillary passes through sheet metal, protect it with a rubber grommet (to prevent shearing).
9. Install the sensor element using capillary supports.
| Method of Installation-1 |
π Related: Humidity Duct Sensor Installation Methods in HVAC System
πConclusion
This first part of the Temperature Sensor Installation Series covered essential sensor types used in HVAC and industrial systems, including immersion, cable, probe, capillary, and averaging sensors. Understanding their installation methods ensures accurate temperature monitoring, improved system reliability, and long-lasting performance.
In the next part, we will explore additional sensor types such as solar sensors, wind sensors, strap-on sensors, outdoor temperature sensors, room sensors, and frost protection sensors.
Stay connected with Insight Control System for more technical and professional automation content.
π¬ We’d love your feedback!
Share your thoughts in the comments below to help improve future posts.
π© Follow Insight Control System for more educational articles on Building Automation & PLC Programming.
π Related: How to Inspect Variable Frequency Drives–Daily and Periodic Maintenance Guide
π Related: Boiler Types and Classifications for Industrial and Commercial Use
π Related: Top 100+ Building Automation System Abbreviations and Their Meanings Part 1
π Related: QElectro Tech Software: Free Electrical Diagram Tool – Full Overview & Guide
π Related: PLC Basic Instructions Explained | Essential Allen-Bradley MicroLogix & PLC-5 Ladder Logic Functions
Comments
Post a Comment